Overview
🔌
Calculators
9
🏗️
Materials
Cu / Al
⚡
Phase Support
1Φ & 3Φ
📐
Standards
IEC / BS
Calculators
📏
Cable Size by Current
Select cable cross-section from load current
I_design = I_load / (Ca × Cg × Ci) | Select cable ≥ I_design
Recommended Cable Size
—
📉
Voltage Drop Calculator
Voltage drop across cable run
VD = (2 × ρ × L × I) / A [1Φ] | VD = (√3 × ρ × L × I) / A [3Φ]
Voltage Drop
—
Drop %
—
Receiving Voltage
—
🔍
Cable Size by Voltage Drop
Min cable size to keep drop within limit
A = (ρ × mult × L × I) / (VD_allowed) [mm²]
Calc. Area
—
Std. Size
—
Actual Drop
—
🔗
Cable Resistance & Impedance
R, X, Z per metre & total
R = ρ × L / A | Z = √(R² + X²) [Ω]
R/m (mΩ)
—
Total R (Ω)
—
Total X (Ω)
—
Total Z (Ω)
—
⚡
Cable Ampacity (Current Capacity)
Rated current capacity with derating
I_rated = I_base × Ca × Cg × Ci [Derating Factors]
Base Rating
—
Temp Factor
—
Group Factor
—
Derated Rating
—
⚠️
Short Circuit Withstand
Min cable size for fault current
A = (I_sc × √t) / k [mm²] Cu: k=115 (PVC), 143 (XLPE)
Min. Area (mm²)
—
Std. Cable Size
—
k Factor
—
🔥
Power Loss in Cable
I²R losses & energy cost
P_loss = I² × R_total [W] | Energy = P × Hours / 1000 [kWh]
Power Loss
—
Loss %
—
Daily Cost
—
Monthly Cost
—
🏗️
Conduit Size Calculator
Conduit size for cable bundles
Fill Ratio ≤ 40% (multi-cable) or 53% (single) | A_conduit ≥ ΣA_cable / fill
Total Cable Area
—
Min. Conduit Ø
—
Std. Conduit Size
—
📋
Cable All-in-One Summary
Complete cable sizing: Current capacity + Voltage drop + Power loss + Conduit — all in one
Complete cable check: Size → Ampacity → VDrop% → Power Loss → Conduit recommendation
Load Current
—
Cable Size (Current)
—
Cable Size (VDrop)
—
Final Recommended
—
Voltage Drop
—
Drop %
—
Power Loss
—
Conduit Size
—