Advanced Generator Calculators – Short Circuit, Load Sharing, Starting kVA & Voltage Regulation | CircuitSecrets
Advanced Generator Engineering Suite
Industrial-Grade Power System Analysis Tools
Generator Short Circuit Current Calculator
Full Load Current (3Φ): I_FL = (S_kVA × 1000) / (√3 × V)
Full Load Current (1Φ): I_FL = (S_kVA × 1000) / V
Short Circuit Current: I_SC = I_FL × (100 / Xd″%)
Fault Level (MVA): S_fault = √3 × V_kV × I_SC / 1000
Where: Xd″ = Subtransient reactance (typically 12-20% for generators)
Reference: IEEE Std 141, IEC 60909
Generator Motor Starting kVA Calculator
Motor Power (kW) = HP × 0.746
Full Load Current: I_FL = (P_kW × 1000) / (√3 × V × η × PF)
Starting Current Multipliers:
• DOL: 5-7 × I_FL (typically 6× used)
• Star-Delta: ~3 × I_FL
• Soft Starter/VFD: 2-3 × I_FL (typically 2.5×)
Required Generator kVA = (I_start × √3 × V) / 1000 × 1.25
Safety Factor: 1.25 (25% margin for voltage stability)
Reference: IEEE Std 399, NEMA MG-1
Generator Parallel Load Sharing Calculator
Total Capacity: S_total = Gen1 + Gen2
Load Share Factor: f1 = Gen1 / S_total, f2 = Gen2 / S_total
Shared Load: L1 = Load × f1, L2 = Load × f2
Loading %: L% = (Shared Load / Generator Rating) × 100
Load Imbalance: |L1% - L2%|
Acceptable Imbalance: < 10% (Good), < 20% (Acceptable), > 20% (Poor)
Optimal Loading: 70-85% of rated capacity per generator
Reference: IEEE Std 399, ISO 8528-5
Generator Voltage Regulation Calculator
Impedance: %Z = √(%R² + %X²)
Load Factor: k = Load% / 100
Voltage Regulation (Lagging PF): %VR = k × [%R × cos(φ) + %X × sin(φ)]
Voltage Regulation (Leading PF): %VR = k × [%R × cos(φ) - %X × sin(φ)]
Where: cos(φ) = Power Factor, sin(φ) = √(1 - PF²)
Acceptable Limits: %VR ≤ 3% (Excellent), ≤ 5% (Acceptable), > 5% (Poor)
Reference: IEEE Std 141, IEC 60034-1
Generator Protection Sizing Calculator
Breaker Rating: I_breaker ≥ 1.25 × I_FL (per NEC 430.52)
Fault Current: I_fault = I_FL × (100 / Xd″%)
Breaking Capacity: I_breaking ≥ I_fault × 1.5 (safety factor)
Standard Ratings: Round up to next standard breaker size
MCB: Up to 125A, 10kA typical breaking capacity
MCCB: 100-3200A, 25-100kA breaking capacity
ACB: 800-6300A, 50-150kA breaking capacity
VCB: 630-5000A, 40-100kA breaking capacity
Reference: IEC 60947-2, IEEE C37.13, NEC Article 430
No comments