MCB / MCCB / ACB Breaker Selection Calculator

MCB / MCCB / ACB Selection Calculator | CircuitSecrets
⚡ CircuitSecrets

MCB / MCCB / ACB Selection Calculator

Professional breaker sizing from load current or load power — with ambient derating, tripping curve, and breaking-capacity verification per IEC 60898/60947.

MCB ≤100A
MCCB 100–630A
ACB >630A
Ambient Derating
Curve B/C/D
Icu Check
Protection Sizing
Breaker Input
Input Mode
Load Current
Load Power
Load Type
Lighting Curve C
Heater / Resistive Curve B
Motor — DOL Start Curve D
Motor — Star-Delta / VFD Curve D
General Distribution Curve C
Load Current
Circuit Conditions
Protection Result
Breaker Selection
Ib — A
MCB/MCCB
Load
Recommended Breaker
Amperes — select inputs and calculate
Nearby Standard Ratings
    Standard Rating Ladder
    Rating (A)TypeTypical Icu
    Formulas & Selection Logic
    Design Current
    Continuous duty: Ib = I × 1.25
    Non-continuous: Ib = I × 1.0
    3-phase power: I = P / (√3 × V × PF × η)
    1-phase power: I = P / (V × PF × η)
    Ambient derate: In(req) = Ib ÷ derating factor
    IEC 60364-433: Ib ≤ In ≤ Iz
    Curves: B resistive · C lighting/distribution · D motor inrush
    Practical Notes & Compliance

    This tool gives a first-pass selection only. Verify against manufacturer datasheets and the applicable local code (IEC 60947/60898, NEC, or BNBC).

    Motors: the rating above sizes thermal/overload protection. Instantaneous (magnetic) or electronic trip settings must be separately checked against actual starting current.

    Cable coordination: the downstream cable must independently satisfy Ib ≤ In ≤ Iz — a correctly sized breaker does not guarantee a correctly sized cable.

    For final circuits feeding sockets or damp-area lighting, add RCD/RCBO protection alongside overcurrent protection.

    ⚠ Note: Ratings based on standard reference conditions (30°C ambient). Apply derating for grouping and installation method as needed. Breaking capacity shown without a fault-level entry is a typical class value only — always verify with a short-circuit study before installation.
    © 2026 CircuitSecrets — MCB / MCCB / ACB Selection Calculator · IEC 60898 · IEC 60947 · IEC 60364

    Post a Comment

    0 Comments
    * Please Don't Spam Here. All the Comments are Reviewed by Admin.