Electrical Safety & BNBC Code Book
Complete reference for BNBC 2020 codes, earthing standards, fire safety, wiring faults, protection systems & test procedures — Bangladesh & IEC standard
BNBC 2020 mandates proper earthing for all electrical installations.
- Electrode depth: Minimum 2.5m for rod electrodes
- Earth resistance: ≤10Ω general, ≤1Ω substations
- Testing: Annual testing mandatory with documentation
- Conductor size: Min 16mm² Cu or 25mm² Al
- Bonding: All metallic enclosures and structural steel must be bonded
Earth Resistance = ≤ 10Ω (general)
Rod Length = ≥ 2.5 m
Conductor = ≥ 16 mm² Cu
Cables must be selected based on load current, installation method and derating per BNBC 2020 Table 8.5.
- Min lighting: 1.5mm² Cu
- Min sockets: 2.5mm² Cu
- Aluminium: Only ≥ 16mm²
- Insulation: PVC 70°C or XLPE 90°C per ambient
- Derating: Temperature, grouping and install method all applied
| Curve | Trip Range | Application |
|---|---|---|
| Curve B | 3–5 × In | Resistive, lighting |
| Curve C | 5–10 × In | Motors, mixed loads |
| Curve D | 10–20 × In | High inrush, transformers |
- PVC conduit: Max 40% fill ratio
- Metal conduit: Must be earthed at both ends
- Bends: Max 4 between draw-in points
- Support spacing: Horizontal max 900mm, vertical max 1200mm
- Damp areas: IP54 rated fittings minimum
| Circuit Type | Demand Factor |
|---|---|
| Lighting (first 3kW) | 100% |
| Lighting (remaining) | 35% |
| Small appliances | 100% first 3kVA |
| AC units | 100% |
| Motors | 125% of FLC |
RCDs are mandatory under BNBC 2020 for:
- Wet/damp locations: 30mA RCD on all socket circuits
- Outdoor circuits: All external — 30mA RCD
- Bathrooms: All circuits within bathroom zones
- Construction sites: 30mA portable tools, 100mA fixed
- Residential: One socket per 3.5m of wall length minimum
- Kitchen: Minimum 2 sockets per counter
- Height: 300–500mm standard; 1100–1300mm accessible
- Wet areas: Min 600mm from water, IP44 rated
- Outdoor: IP65 minimum, RCD protected
- Spare ways: Minimum 25% spare MCB ways
- Main switch: Accessible and lockable
- Labeling: All circuits labeled with load description
- Height: 1.4–1.8m from finished floor level
- Enclosure: IP30 indoor, IP54 damp/outdoor
| Type | Description | Best For |
|---|---|---|
| Plate Electrode | GI/copper plate ≥3m deep | Low current, stable soil |
| Rod Electrode | 25mm dia, ≥2.5m deep | Rocky soil, easy install |
| Ring Electrode | Bare conductor ring around building | Large buildings, substations |
| Strip Electrode | Horizontal strip ≥600mm depth | Low resistivity areas |
| Pipe Electrode | 38mm GI pipe, 2.5m deep | Common residential BD |
| Installation Type | Max Resistance |
|---|---|
| General residential | ≤ 10 Ω |
| Commercial building | ≤ 5 Ω |
| Industrial / substation | ≤ 1 Ω |
| Hospital / data center | ≤ 0.5 Ω |
| IT equipment (clean earth) | ≤ 1 Ω |
| System | Description | Common Use |
|---|---|---|
| TN-S | Separate N and PE throughout | Commercial, preferred |
| TN-C-S | PEN combined then split at DB | Residential BD common |
| TT | Separate earth at premises | Rural, no PEN available |
| IT | Isolated neutral, local earth | Hospital operating theatres |
Fall of Potential Method (3-point method) — standard IEC test:
- Drive current electrode (C) at ≥30m from earth electrode (E)
- Drive potential electrode (P) at 62% of C-E distance
- Measure with earth tester; take 3 readings, move P ±10%
- Average = final result
- Main bonding: All metal services (water, gas, structural) to MET
- Supplementary: Bathrooms — all metallic items within 2.5m bonded
- Bond conductor: Min 6mm² Cu supplementary, 10mm² Cu main
- MET: Accessible for disconnection and testing
- Multiple rods: Parallel rods spaced ≥2× rod length apart
- Salt treatment: Charcoal + salt backfill — temporary improvement
- Bentonite: Chemical earthing compound — permanent, moisture retentive
- Deeper electrode: Drilling to moist subsoil layers
- Ring earth: Larger ring area reduces effective resistance
| Type | Color | Electrical Fire | Notes |
|---|---|---|---|
| CO² | Black label | ✓ YES | Best for live electrical — no residue |
| Dry Powder | Blue label | ✓ YES | Effective but leaves residue |
| Water | Red | ✗ NO | NEVER on live circuits |
| Foam | Cream label | ✗ NO | Conductive — do not use on live |
- Raise alarm — Alert all occupants immediately
- Isolate power — Switch off at main DB if safe
- Evacuate — All personnel leave the area
- Call 999 — Fire brigade (Bangladesh emergency)
- Extinguish — Use CO² only if trained and safe
- Do not re-enter — Until certified safe by fire service
- Overloaded circuits: Too many appliances — insulation fails
- Loose connections: Arcing at terminals generates intense heat
- Undersized cables: Excessive current melts insulation
- Rodent damage: Chewed cable — very common in Bangladesh
- Old wiring: PVC degrades after 20–25 years
- Smoke detectors: All sleeping areas and corridors
- Heat detectors: Kitchens (avoids false alarms from smoke)
- Placement: Ceiling, ≥300mm from walls, ≤7.5m spacing
- Interconnection: All detectors should be interconnected
- Testing: Monthly push-button test, annual professional inspection
- FP200 / FR cable: 90 min fire resistance at 950°C — for emergency circuits
- MICC (Pyro): Mineral insulated — withstands >1000°C
- Required for: Emergency lighting, fire alarm, smoke extraction circuits
- Installation: Dedicated routes away from normal wiring
Symptoms: Intermittent power, sparking, burn marks, warm switches.
Cause: Vibration, thermal cycling, improper torque during installation.
Fix: Isolate, re-tighten all terminals to spec (typically 1–3 Nm). Replace burnt terminals.
Symptoms: Voltage fluctuations, lights bright/dim, appliance damage.
Cause: Overloaded neutral in 3-phase system, loose neutral at service head.
Fix: Locate and replace damaged neutral. Check DB, service head, all connections. Balance loads.
Symptoms: RCD tripping, shock from metalwork, MCB tripping under load.
Test: Insulation resistance test (Megger) — minimum 1MΩ at 500VDC.
Test Voltage = 500 V DC
New wiring = ≥ 200 MΩ
Symptoms: Instantaneous MCB trip, loud bang, burn smell, visible damage.
Cause: Direct contact between line and neutral, insulation damage.
Fix: Do NOT reset without finding fault. Use insulation tester to locate. Replace damaged section.
Symptoms: MCB trips after time delay, warm cable, discolored outlets.
Cause: Total load exceeds circuit rating. Common in BD with increased AC use on old wiring.
Fix: Calculate total load, redistribute circuits, upgrade cable and MCB if needed.
Symptoms: Shock risk even when switch is off, some appliances malfunction.
Cause: Live and neutral swapped at socket, DB or luminaire.
Fix: Swap connections at the outlet or DB. Verify polarity at all outlets with socket tester.
Symptoms: Dim lights at end of long runs, motor overheating, equipment malfunction.
V_drop = 2 × I × ρ × L / A
Fix: Upsize cable or reduce run length. Split long circuits.
| Device | Range | Breaking Cap. | Use |
|---|---|---|---|
| MCB (B/C/D) | 6–125A | 6–10 kA | Residential, commercial |
| MCCB | 16–1600A | Up to 100 kA | Industrial, large panels |
| ACB | 400–6300A | Up to 150 kA | HV switchgear, incomers |
| HRC Fuse | 2–1250A | Up to 80 kA | Motor protection, backup |
| Sensitivity | Trip Time | Application |
|---|---|---|
| 10 mA | <30ms | Swimming pools, medical |
| 30 mA | <40ms | Standard personal protection |
| 100 mA | <150ms | Fire protection |
| 300 mA | <150ms | Equipment protection only |
- Type 1 SPD: Service entry — handles direct lightning strike current
- Type 2 SPD: Main DB — switching surges and indirect strikes
- Type 3 SPD: Socket/equipment — fine protection for sensitive devices
- Uc rating: Must exceed nominal voltage × 1.1 minimum
- Thermal overload relay: Set to 100–115% of motor FLC
- Short circuit: HRC fuse or MCCB — rated ≤ 250% FLC
- Phase failure relay: Protects 3-phase motors from single phasing
- Thermistor: Embedded in winding for direct temperature protection
Arc flash releases enormous energy — temperatures can reach 20,000°C.
- PPE: Arc flash suit, face shield, insulated gloves mandatory
- AFDD: Arc Fault Detection Devices detect dangerous wiring arcing
- Warning labels: All panels must show arc flash warning with incident energy data
- Identify all energy sources
- Notify affected personnel
- Isolate circuit at source
- Apply lockout device + personal padlock
- Apply danger tag
- Verify dead with approved voltage tester
| System Voltage | Test Voltage | Min IR Value |
|---|---|---|
| SELV (<50V) | 250V DC | ≥0.5 MΩ |
| Up to 500V | 500V DC | ≥1 MΩ |
| 501V – 1000V | 1000V DC | ≥1 MΩ |
- Protective conductor: <1Ω from MET to furthest point
- Ring final circuit: Check live, neutral and CPC separately
- Bonding conductors: Typically <0.05Ω
- Equipment: Low resistance ohmmeter or MFT continuity function
- All single-pole switches in line conductor only
- Centre contact of E-screw lamps on line
- Socket outlet pins correctly identified
Line (L) = Red (old) / Brown (new)
Neutral (N) = Black (old) / Blue (new)
Earth (E) = Green / Yellow
Zs determines fault current available to operate protective devices.
Fault current = Uo / Zs
/* Uo = 230V (nominal line voltage) */
Zs must be low enough to ensure fault current exceeds MCB trip threshold within 0.4s (socket circuits).
| Equipment | Tests | Standard |
|---|---|---|
| MFT (Multifunction Tester) | IR, continuity, loop, RCD | IEC 61557 |
| Earth Tester | Earth electrode resistance | IEC 60364 |
| Clamp Meter | Current, leakage current | IEC 61010 |
| Power Analyser | PF, harmonics, THD | IEC 61000 |
| Thermal Camera | Hot joints, overloads | IEC 60068 |
