Professional Power System Calculations for Engineers, Consultants & EPC Contractors
Power Factor Correction Calculator
Calculate the required capacitor bank size (kVAR) to improve power factor from existing to desired value. Complies with IEEE 141 and IEC 60831 standards.
C (μF) = (kVAR × 10⁹) / (2 × π × f × V²) [for single-phase]
C (μF) = (kVAR × 10⁹) / (3 × 2 × π × f × Vₗₗ²) [for three-phase]
Transformer Sizing Calculator
Determine the appropriate transformer kVA rating based on load requirements, future expansion, and safety margins. Complies with IEEE C57.12.00 and IEC 60076 standards.
Required kVA = (Load kVA / Load Factor) × (1 + Future Expansion/100) × (1 + Safety Margin/100)
Select next standard transformer size ≥ Required kVA
- 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000
- 5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500
Generator (DG) Sizing Calculator
Calculate the required generator size considering motor starting currents, load diversity, and future expansion. Complies with ISO 8528 and IEEE 446 standards.
Starting kVA = Largest Motor kW × Starting Multiplier / PF_motor
Required Generator kVA = MAX(Running kVA × (1+Expansion/100), Starting kVA)
Apply 10-20% safety margin for continuous operation
Solar Motor Load Calculator
Size a solar PV system to power motor loads considering daily energy requirements, solar irradiance, and system losses. Complies with IEC 62446 and IEEE 1547 standards.
Adjusted Energy (kWh) = Daily Energy Required / [(1 - System Losses/100) × Inverter Efficiency]
PV Array Size (kWp) = Adjusted Energy / Solar Irradiance
Number of Panels = PV Array Size (W) / Panel Rating (W)
Short Circuit Current Calculator
Calculate symmetrical short circuit current at transformer secondary terminals. Complies with IEC 60909 and ANSI/IEEE C37.010 standards for protective device coordination.
With utility contribution: I_sc_total = 1 / √[(1/I_sc_utility)² + (1/I_sc_transformer)²]
Asymmetrical current = I_sc_symmetrical × √[1 + 2e^(-2π/(X/R))]
