Header Ads

Header ADS

Advanced Power System Calculator – PFC, Transformer & Generator Sizing

CircuitSecrets | Professional Power System Calculators

Professional Power System Calculations for Engineers, Consultants & EPC Contractors

Professional Engineering Tools - Ad Space (Blogger/AdSense Safe)

Power Factor Correction Calculator

Calculate the required capacitor bank size (kVAR) to improve power factor from existing to desired value. Complies with IEEE 141 and IEC 60831 standards.

kilowatts (kW)
decimal (0.1-0.99)
decimal (0.8-0.99)
volts (V)
hertz (Hz)
configuration
kVAR = kW × [tan(cos⁻¹(PF₁)) - tan(cos⁻¹(PF₂))]
C (μF) = (kVAR × 10⁹) / (2 × π × f × V²) [for single-phase]
C (μF) = (kVAR × 10⁹) / (3 × 2 × π × f × Vₗₗ²) [for three-phase]
Standards Compliance: IEEE 141 (Red Book), IEC 60831, and NEC Article 460. Capacitor banks should include discharge resistors and overcurrent protection.
Required Capacitor Bank
0.00
kVAR
Capacitor Current
0.00
Amperes (A)
Capacitance Value
0.00
Microfarads (μF)
Power Factor Improvement
0.00
% Reduction in Current
Engineering Note: Always install capacitors at the load terminals or use automatic power factor correction panels for varying loads. Verify harmonic conditions before installation to avoid resonance issues.

Transformer Sizing Calculator

Determine the appropriate transformer kVA rating based on load requirements, future expansion, and safety margins. Complies with IEEE C57.12.00 and IEC 60076 standards.

kilowatts (kW)
decimal (0.1-1.0)
decimal (0.1-1.0)
percent (%)
percent (%)
configuration
Load kVA = (Load kW) / PF
Required kVA = (Load kVA / Load Factor) × (1 + Future Expansion/100) × (1 + Safety Margin/100)
Select next standard transformer size ≥ Required kVA
Standards Compliance: IEEE C57.12.00, IEC 60076, and NEC Article 450. Transformers should be derated for harmonic loads and high ambient temperatures.
Calculated kVA Requirement
0.00
kVA
Recommended Transformer Size
kVA (Standard Size)
Utilization at Full Load
0.00
percent (%)
Load Current (Full Load)
0.00
Amperes (A)
Standard Three-Phase Transformer Sizes (kVA):
  • 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000
Standard Single-Phase Transformer Sizes (kVA):
  • 5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500
Engineering Note: For non-linear loads (VFDs, computers), apply a K-factor derating. For continuous loads, ensure transformer is rated for 100% duty cycle. Always verify impedance requirements for fault current calculations.

Generator (DG) Sizing Calculator

Calculate the required generator size considering motor starting currents, load diversity, and future expansion. Complies with ISO 8528 and IEEE 446 standards.

kilowatts (kW)
decimal (0.1-1.0)
kilowatts (kW)
starting current multiplier
decimal (0.5-1.0)
percent (%)
Running kVA = (Total Load kW / PF) / Diversity Factor
Starting kVA = Largest Motor kW × Starting Multiplier / PF_motor
Required Generator kVA = MAX(Running kVA × (1+Expansion/100), Starting kVA)
Apply 10-20% safety margin for continuous operation
Standards Compliance: ISO 8528, IEEE 446 (Orange Book), and NFPA 110. Generator sets should be sized to handle the largest motor starting without exceeding 30% voltage dip.
Running Load kVA
0.00
kVA
Motor Starting kVA
0.00
kVA
Required Generator Size
0.00
kVA
Engineering Note: For critical applications, consider N+1 redundancy. Verify fuel consumption at expected load levels. Ensure proper harmonic filtering for VFD loads. Always perform a detailed load analysis including inrush currents for all motors.

Solar Motor Load Calculator

Size a solar PV system to power motor loads considering daily energy requirements, solar irradiance, and system losses. Complies with IEC 62446 and IEEE 1547 standards.

kilowatts (kW)
decimal (0.5-0.98)
hours per day
kWh/m²/day
percent (%)
decimal (0.8-0.99)
Daily Energy Required (kWh) = (Motor Power / Motor Efficiency) × Operating Hours
Adjusted Energy (kWh) = Daily Energy Required / [(1 - System Losses/100) × Inverter Efficiency]
PV Array Size (kWp) = Adjusted Energy / Solar Irradiance
Number of Panels = PV Array Size (W) / Panel Rating (W)
Standards Compliance: IEC 62446, IEEE 1547, and NEC Article 690. Systems must include proper grounding, overcurrent protection, and rapid shutdown capabilities.
Daily Energy Required
0.00
kWh/day
Required PV Array Size
0.00
kWp
Number of Panels (350W)
0
panels
Battery Capacity (12V)
0.00
Ah (for 1-day autonomy)
Engineering Note: For motor loads, consider soft starters or VFDs to reduce inrush current. Battery sizing assumes 50% depth of discharge for lead-acid batteries. For lithium-ion, reduce capacity by 30%. Always include 20-25% additional capacity for cloudy days.

Short Circuit Current Calculator

Calculate symmetrical short circuit current at transformer secondary terminals. Complies with IEC 60909 and ANSI/IEEE C37.010 standards for protective device coordination.

kVA
volts (V)
percent (%)
ratio
MVA (at primary)
configuration
I_sc (kA) = (Transformer kVA × 100) / (√3 × V_ll × Z%) [ignoring utility contribution]
With utility contribution: I_sc_total = 1 / √[(1/I_sc_utility)² + (1/I_sc_transformer)²]
Asymmetrical current = I_sc_symmetrical × √[1 + 2e^(-2π/(X/R))]
Standards Compliance: IEC 60909, ANSI/IEEE C37.010, and NEC Article 110.9. Protective devices must have interrupting ratings exceeding the available fault current at their installation point.
Symmetrical SC Current
0.00
kA (RMS)
Asymmetrical SC Current
0.00
kA (Peak)
SC Current with Utility
0.00
kA (RMS)
Min. Breaker Interrupting Rating
0.00
kA
Engineering Note: Always verify actual utility fault levels with the power company. For motors contributing to fault current, add 4-6x motor FLA for first cycle calculations. Arc flash studies require detailed system modeling beyond this simplified calculation.
Professional Engineering Tools - Ad Space (Blogger/AdSense Safe)

CircuitSecrets Power System Calculators | Professional Engineering Tools for Electrical Consultants & EPC Contractors

DISCLAIMER: These calculators are for estimation purposes only. Results are based on standard engineering formulas and typical assumptions. Always verify calculations with manufacturer data, detailed system studies, and local electrical codes (NEC, IEC, BS, etc.) before implementation. CircuitSecrets assumes no liability for errors or omissions. Professional engineering judgment is required for all critical applications.

© 2023 CircuitSecrets Engineering Tools | IEEE / IEC / BS Standards Compliant Calculations

No comments

Powered by Blogger.