Transformer Engineering &
Economic Analysis Platform
Professional power system analysis for utilities, substations & EPC contractors — six integrated modules covering fault protection, ROI, thermal aging, arc flash safety, voltage stability & parallel simulation.
🎯 Enterprise Engineering Dashboard
Comprehensive transformer analysis platform combining fault protection, economic optimization, thermal management, arc flash safety, voltage stability & parallel operation simulation. Click any module card below to open its workspace.
Fault & Protection
Coordination Engine
Economic Loss
ROI Analyzer
Thermal Aging
Insulation Life Model
Arc Flash Risk
Safety Estimator
Voltage Stability
Regulation Analyzer
Parallel Operation
System Simulator
⚡ Fault & Protection Coordination Engine
Calculate fault currents & verify protection device coordination for relay settings, breaker selection & fault interruption capacity
X: Z/√(1+1/XR²) · R: X/XR
κ: 1.02 + 0.98×e^(−3R/X) · I p: κ×√2×I k"
Fault MVA: √3 × V_kV × I k"
IEC 60909-0 Clause 4 · IEC 60947-2 · IEEE C37.04
💰 Economic Loss & ROI Analyzer
Lifecycle cost analysis & ROI for transformer selection — compare high-efficiency vs. standard transformers
Annual kWh: P_total × 8760 / 1000
Payback: Premium / Annual_Savings
ROI: [(Lifetime_Savings − Premium) / Premium] × 100
IEC 60076-1 Clause 7 — Loss evaluation
🌡️ Thermal Aging & Insulation Life Model
Estimate aging rate & remaining life based on thermal loading — critical for asset management & overload planning
Hot-Spot: Θ_amb + ΔΘ_o + H×k^m
F_AA: e^[15000/383 − 15000/(Θ_h+273)]
IEEE V: 2^[(Θ_h−98)/6]
IEEE C57.91 Clause 7 · IEC 60076-7
🔥 Arc Flash Risk Estimator
Estimate incident energy & PPE requirements — critical for worker safety during maintenance operations
E: 4.184 × C_f × P × (t / D²)
C_f: 1.0 open · 1.3 cable · 1.5 switchgear
PPE Cat: 0<1.2 · 1<4 · 2<8 · 3<25 · 4>25 cal/cm²
IEEE 1584 simplified · NFPA 70E
📊 Voltage Stability & Regulation Analyzer
Analyze voltage regulation under varying load & power factor — tap changer sizing, reactive power compensation
Lagging: k×[%R×cosφ+%X×sinφ]
Leading: k×[%R×cosφ−%X×sinφ]
Limits: <2% Excellent · <5% Acceptable · >5% Action Required
IEC 60076-1 Clause 6
🔄 Parallel Transformer System Simulator
Load sharing, circulating current & suitability — advanced compatibility verification & load imbalance analysis
Load Share: f_i = (1/Z_pu,i) / Σ(1/Z_pu)
Criteria: same vector group · Δ%Z/%Z_avg <7.5% good · <10% ok
IEEE C57.12.00 Section 6